t.jpg (20590 bytes)
UNINTERRUPTIBLE POWER SYSTEMS
S-series---M-series---SR-series

 

SPECIFICATION
MODEL M1010 M1020 M1030 M1050 MS1075
MS3075
MS1100
MS3100
MS1120
MS3120
MS3150 MS3200
Rated Power at p.f.=0.8 1KVA 2KVA 3KVA 5KVA 7..5KVA 10KVA 12KVA 15KVA 20KVA
Input Voltage 100V/110V/120V/?15%OR220V/230V/240V/?15% 220V/230V/240V/?15%or 380V/220V,400V/230V415V/240V?15%
Frequency 50Hz or 60Hz ? 5%
phase 1?2w+G 1?2w+G  or   3?3w+G  or  3?4w+G
Output Voltage 100V/110V/120V or 220V/230V/240V 220V/230V/240V
Phase 1?2w+G
Voltage regulation ? 1%
Frenquency 50Hz  or  60Hz
Frenquency stability ? 0.5 %
Transient Condition ? 4% For 100% instantaneous load variation, recover to ? 1%after 25ms.
Harmonic distortion v.gif (171 bytes) 3%At100% linear load
Waveform Sinewave
Crest ratio 3:1
Overload capability 150% For 25 seconds
Efficiency Complete unit >73% >80% >82% >83% >84%
inverter >85% >90%
Battery DC Voltage 84VDC 144VDC 192VDC
Type 12V7AH 12V7AH 12V7AH 12V7AH 12V7AH 12V26AH 12V26AH 12V40AH 12V40AH
Rechargeable, Sealed maintenance free
Back-up time
at full load
15 min. 15min. 12 min. 17 min. 10 min. 12 min. 10 min. 12 min. 8 min.
Recharge time 10 hours to 90% after fully discharged
Battery completely
discharge
Auto cut-off invert
invert auto-restart when line recovers
Transfer time Line fail or recover Zero
UPS TO BY-PASS
or reverse
<2ms. At full load
UPS fault <2ms. Transfer to by-pass
Overload <2ms. Transfer to by-pass, auto-transfer to inverter 25 secs after decreasing load
Audible noise At one meter <55dBA <60dBA
Indicators Five LED'S
Two levels
Line input (green), Battery (green), Inverter (green), Bypass (amber), Fault (red)
Battery capacity level & load capacity level
Audible alarm Battery discharge Sounding every four seconds after line fails (alarm can be silenced by pushing the reset button)
Sounding once every one second as battery approaches final discharge (alarm can not be silenced)
Fault Continuous (cannot be silenced)
Environment Temperature 0?C ~ 40?C (32?F~ 104?F)
Humidity 30% ~ 90% (non-condensing)
Weight (kgs) Without Battery 455 61 81 102.5 141 173 173 212.5 282.5
Internal Battery 18.5 32 43   100        
ISO. TX.       47 39 65 66 61  
Total (kgs) 64 93 124 149.5 280 238 239 273.5 282.5
Dimension L?W?H (mm) 520?250
?510
520?250
?530
655?270
?700
655?270
?700
700?490
?883
700?490
?883
700?490
?883
700?490
?883
700?490
?883
Option:
MODEL
BATTERY
M1050 MS1075
MS3075
MS1100
MS3100
MS1120
MS3120
MS3150 MS3200 Dimension
L?W?H(mm)
Cabinet Batt.. Total
Weight(kgs)
12V 7AH Battery Bank 17min     - - - 660?270?680 35 80 115
12V 26AH Battery Bank - 21mins 12mins 10min 8min - 700?350?840 66 152 218
12V 40AH Battery Bank - 35mins 20mins 15min 12min 8min 700?430?840 66 245 311
Supports NOVELL, UNIX system users via a DB9 connector.

 